VERSION WITH SEPARATE BATTERY BOX
ENTRANCE
Rated voltage: 380-400-415 Vac three-phase + N
Nominal frequency: 50/60 Hz
Frequency tolerance: 40 ÷ 72 Hz
Power factor at full load: 0.99
Current distortion: THDI ≤ 3%.
BY-PASS
Rated voltage: 380-400-415 Vac three-phase + N
Number of phases: 3 + N
Voltage tolerance: 180 ÷ 264 V (selectable)
Rated frequency: 50 or 60 Hz (selectable)
Frequency tolerance: ±5 (selectable)
EXIT
Rated power: 125 kVA
Active power: 112.5 kW
Power factor: 0.9
Number of phases: 3 + N
Rated voltage: 380-400-415 Vac three-phase + N (selectable)
Static variation: ± 1%
Dynamic variation: ± 3%
Crest factor: 3 : 1 Ipeak/Irms
Voltage distortion: ≤ 1% with linear load / ≤ 3% with distorting load
Frequency: 50/60 Hz
Frequency stability in battery: 0.01%.
Supported battery type: VRLA AGM/GEL/NiCd/Li-ion/Supercaps
recharge time: 6 hours
Weight without batteries (kg): 250
Depth: 840 mm
Width: 650 mm
Height: 1600 mm
Communication: 3 slots for communication interface /RS232/USB
Ambient temperature: 0 °C/ +40 °C
Relative humidity: 90% non-condensing
Colour: Dark grey RAL 7016
Noise level at 1 meter: < 63 dB(A)
Degree of protection: IP20
Smart Active Yield: up to 99%
With wheels for handling