RIELLO SENTRYUM S3T ACT 10 UPS 10 KW THREE-PHASE
INPUT
Voltage (V): 380 / 400 / 415 three-phase + N
Frequency: 50 / 60 hZ
Current Distortion: THDI ≤3%
BYPASS
Voltage (V): 380 / 400 / 415 three-phase + N
Phase type: Three-phase
Frequency: 50 or 60 Hz (selectable)
Bypass overload: 110% infinite, 125% for 60 min, 150% for 10 min.
OUTPUT
Phase type: three-phase
Power: 10 KVA
Active power: 10 KW
Power factor: 1 up to 40 °C
Rated voltage (V): 380 / 400 / 415 three-phase + N (selectable)
Rated frequency: 50 or 60 Hz (selectable)
BATTERIES
Type: VRLA AGM/GEL/NiCd/Li-Ion/SuperCaps
Charging method: One level, two levels, cyclic charging (selectable)
GENERAL SPECIFICATIONS
Length: 380 mm
Depth: 850 mm
Height: 1025 mm
Weight without batteries: 72 Kg
- Phase
- Three phase
- Frequency (Hz)
- 50 / 60
- Voltage (V)
- 380-400-415 + N
- Protection degree
- IP20
- Power (VA)
- 10000
- Battery type
- AGM/GEL/NiCd/Li-ion/Supercaps
- Operating temperature (°C)
- 0 °C / +40 °C
- Running time (h)
- 30 min
- Acoustic pressure
- 40 dB(A) 1 mt.
- Length (mm)
- 850
- Width (mm)
- 380
- Height (mm)
- 1025
- Dry weight (Kg)
- 72
- Colour
- Grey
RIELLO SENTRYUM S3T ACT 10 UPS 10 KW THREE-PHASE
The UPS RIELLO SENTRYUM S3T ACT 10 threephase is capable of delivering a selectable voltage between 380V / 400V / 415V for a maximum power of 10 KW.
This UPS offers the best combination of energy efficiency and overall performance with the additional guarantee of considerable savings in terms of installation and operating costs.
RIELLO SENTRYUM S3T ACT 10 UPS is designed and manufactured with state-of-the-art technologies and components, implementing advanced technologies such as dual core DSP (Digital Signal Processor) microprocessor, three-level inverter circuits and resonant control to ensure maximum protection of critical loads with minimum impact on downstream systems and optimized energy savings.
RIELLO SENTRYUM S3T ACT 10 is a true ON-LINE double conversion UPS system that delivers the highest levels of available power and flexibility, combined with unmatched energy efficiency and superior performance for small data centers and mission critical applications.
The UPS provides maximum available power without derating. Thanks to the three-level IGBT inverter topology (based on modules instead of discrete components) and innovative digital control.
RIELLO SENTRYUM S3T ACT 10 features a full-color graphical touch screen for displaying UPS information, measurements, operating statuses and alarms in multiple languages. The default screen displays the status of the UPS, various graphic indicators related to the energy path through the UPS and the operating conditions of the various components (rectifier, batteries, inverter, bypass) inside the UPS.
In addition, the user interface includes a UPS status LED bar that provides immediate and clear information about the overall status of the UPS by changing color (blue, blue. orange and red) based on the operating mode and conditions.
CARACTERISTICS UPS RIELLO SENTRYUM S3T ACT 10
INPUT
Voltage (V): 380 / 400 / 415 threephase + N
Frequency: 50 / 60 hZ
Current Distortion: THDI ≤3%
BYPASS
Voltage (V): 380 / 400 / 415 threephase + N
Phase type: Threephase
Frequency: 50 or 60 Hz (selectable)
Bypass overload: 110% infinite, 125% for 60 min, 150% for 10 min.
OUTPUT
Phase type: threephase
Power: 10 KVA
Active power: 10 KW
Factor: 1 up to 40 °C
Rated voltage (V): 380 / 400 / 415 threephase + N (selectable)
Rated frequency: 50 or 60 Hz (selectable)
BATTERIES
Type: VRLA AGM/GEL/NiCd/Li-Ion/SuperCaps
Charging method: One level, two levels, cyclic charging (selectable)
GENERAL SPECIFICATIONS
Length: 380 mm
Depth: 850 mm
Height: 1025 mm
Weight without batteries: 72 Kg
Are you looking for a UPS with different technical characteristics? Visit our section dedicated to UPS and choose the one that best suits your needs.
Images and technical data are not binding and may be subject to revision by the manufacturer
- Phase
- Three phase
- Frequency (Hz)
- 50 / 60
- Voltage (V)
- 380-400-415 + N
- Protection degree
- IP20
- Power (VA)
- 10000
- Battery type
- AGM/GEL/NiCd/Li-ion/Supercaps
- Operating temperature (°C)
- 0 °C / +40 °C
- Running time (h)
- 30 min
- Acoustic pressure
- 40 dB(A) 1 mt.
- Length (mm)
- 850
- Width (mm)
- 380
- Height (mm)
- 1025
- Dry weight (Kg)
- 72
- Colour
- Grey