INPUT
Nominal power: 30KVA
Voltage: 380/400/415 VAC three-phase + N + ground
Input voltage variation: ± 20%
Frequency: 40 / 72 Hz
Power factor: 0.99
Maximum input current phase/neutral: 45 A
Harmonic distortion:< 3%
BY - PASS
Rated voltage: 380/400/415 VAC three-phase + N + earth
Voltage variation: ± 15% (selectable from ± 5% to ± 25%)
Frequency: 50/60 Hz
Rated current: 200% In
Number of phases: 3+N
Protection: short circuit - over load - over temperature
OUTPUT
Nominal power: 30 KVA
Active power: 24 KW
Number of phases: 3+N
Crest factor:3:1
Waveform: sinusoidal
Static stability: ±1%
Dynamic stability: ± 1%
Phase/neutral output current: 38 A
Frequency: 50/60 Hz selectable and/or automatic
Distortion on linear load: 1%
Non-linear load distortion: 3%
Dimensions mm: 500 x 800 x1100 h
Weight without batteries in Kg: 115
Weight of metal cabinet in Kg: 150