CGM 1020B HOOD WITH AUTOMATIC CONTROL UNIT
Maximum power Three-phase: 898 KW
Power continuous use Three-phase: 816 KW
Maximum power Three-phase: 1122 KVA
Three-phase continuous use power: 1020 KVA
Frequency: 50 Hz
Voltage: 400 V + N
Current A: 1472 A
Power factor cos: 0.80
Electrical protection: IP44
Engine: BAUDOUIN 12M26G1100/5
Fuel: Diesel
Displacement cc: 31800 cc
Engine revs: 1500 rpm
Bore x stroke: 150 x 150 mm
Suction: Turbo
Speed controller: Electronic
Number and arrangement of cylinders: V12
Cooling system: Water
Starting: Electric
Alternator: MARELLI MOTORI / MECC ALTE / STAMFORD Without brushes
Poles : 4
Voltage regulator : AVR
Consumption: 154 Lt/h at 75% of load / 205 Lt/h at 100% of load
Tank capacity: 400 Lt
Autonomy: 2.6 h at 75% of the load
Acoustic pressure: 70 dB(A) at 7 mt
Length: 5450 mm
Width: 2200 mm
Height: 2550 mm
Weight: 9040 Kg
- Phase
- Three phase
- Maximum power three phase (KW)
- 898
- Continuous power three phase (KW)
- 816
- Maximum power three phase (KVA)
- 1122
- Continuous power three phase (KVA)
- 1020
- Fuel
- Diesel
- Frequency (Hz)
- 50
- Voltage (V)
- 400
- Engine
- PERKINS 4008 TAG2A
- Emissions Regulations
- Stationary Use
- Engine rpm (rpm)
- 1500
- Speed governor
- Electronic
- Starting system
- Electric
- Engine capacity (cm³)
- 31800
- Number cylinders
- 12
- Cooling
- Water
- Alternator
- Brushless
- Poles
- 4
- Protection degree
- IP44
- Bore x stroke (mm)
- 150 x 150
These generating sets are equipped with Lombardini, Kohler, Perkins, Fpt, Fpt, Doosan, Deutz, Volvo Diesel engines, with electric starter with battery, half bell coupling and reed coupling, mounted on a fixed base, with anti-vibration mounts, fuel tank incorporated in the crankcase.
Electrical panel for manual control, fixed on the group, with the following instrumentation: circuit breaker, voltmeter, 1 or 3 ammeters (depending on the power), hour meter, frequency meter, starting key, optical signal for low oil pressure, high water temperature, battery charger dynamo, minimum fuel level, with automatic stop in case of anomalies, socket or terminal board use.
On request: automatic switchboards, slow or fast towing trolleys (to be registered), protective hoods, soundproof hoods, special equipment.
Images and technical data not binding.
- Phase
- Three phase
- Maximum power three phase (KW)
- 898
- Continuous power three phase (KW)
- 816
- Maximum power three phase (KVA)
- 1122
- Continuous power three phase (KVA)
- 1020
- Fuel
- Diesel
- Frequency (Hz)
- 50
- Voltage (V)
- 400
- Engine
- PERKINS 4008 TAG2A
- Emissions Regulations
- Stationary Use
- Engine rpm (rpm)
- 1500
- Speed governor
- Electronic
- Starting system
- Electric
- Engine capacity (cm³)
- 31800
- Number cylinders
- 12
- Cooling
- Water
- Alternator
- Brushless
- Poles
- 4
- Protection degree
- IP44
- Bore x stroke (mm)
- 150 x 150